消防報警系統必須要安裝隔離模塊嗎

來源:北京消防改造公司  時間:2020-11-12 17:20:31

隔離模塊的作用簡單來說,當信號總線出現短路時,隔離模塊將自動切斷短路部分與總線的連接,短路故障排除后模塊自動恢復正常運行;當雷擊(直擊雷、感應雷)的高電流及高電壓時通過信號總線,擊穿后端若干設備,傳輸至隔離模塊,將把隔離模塊上型號為4148的二極管擊穿,隔離模塊前端(回路板信號輸出端)與后端(信號總線)斷開,從而達到保護回路板不被擊壞的目的。隔離模塊被擊穿的二極管可自行更換,只需排除后端短路故障就可開機運行。
由于隔離模塊有一定保護作用,圖紙設計都有隔離模塊,根據工程規?;蛘呤敲總€回路一個,或者是每層一個,或者是每個區域一個。