防火門維修

消防系統中防火門監控設置要求

來源:北京消防改造公司  時間:2019-12-19 16:22:37

消防系統中防火門監控設置要求

1 防火門監控器應設置在消防控制室內,未設置消防控制室時,應設置在有人值班的場所。
防火門的啟閉在人員疏散中起到至關重要的作用,因此防火門監控器應設置在消防控制室內,沒有消防控制室時,應設置在有人值班的場所。
2 電動開門器的手動控制按鈕應設置在防火門內側墻面上,距門不宜超過 0.5m ,底邊距地面高度宜為 0.9m~1.3m 。
電動開門器的手動控制按鈕應設置在防火門附近的內側墻面上,方便疏散人員逃離火災現場時使用,規定底邊距地面高度宜為 0.9m~1.3m 是為便于疏散人員的觸摸。
3 防火門監控器的設置應符合火災報警控制器的安裝設置要求。
防火門監控器的設置與火災報警控制器的安裝設置要求一致。

 